  • Máy kiểm tra điện trở DC biến áp ba mạch UHV-S10A

    Thiết bị có dòng điện đầu ra lớn và có thể tự động chọn dòng điện; thuận tiện cho việc vận hành. Sở hữu mạch bảo vệ hoàn hảo, độ tin cậy cao. Vỏ nhựa công nghiệp nhẹ; thuận tiện cho việc mang theo.

    Product Details of UHV-S10A Three-circuit Transformer DC Resistance Tester


    Product Introduction

    This DC resistance rapid tester is the latest generation product for measuring the DC resistance of transformers, optimized for measuring the DC resistance of three-phase windings in large capacity transformers. Simultaneously test the DC resistance of the three-phase winding of the transformer.


    Các thông số kỹ thuật

    Testing currentSingle phase:1A 5A 10A 20A
    Three phase:1A 5A 10A
    Measurement scopeSingle phase
    1A 10mΩ ~ 20Ω
    5A 1mΩ ~ 4Ω
    10A 1mΩ ~ 2Ω
    20A 1mΩ ~ 1Ω
    Three phase
    1A 10mΩ ~ 6Ω (each phase)
    5A 1mΩ ~ 1Ω (each phase)
    10A 1mΩ ~ 0.6Ω (each phase)
    Đo lường độ chính xác± (0.2%Full span ± 2 words )
    Maximum resolution0,1mΩ
    Data storage capacity150 groups
    Nguồn cấpAC 220V±22V,50Hz±2Hz
    Môi trường làm việcAmbient temperature: 0°~40° Relative humidity :≤80%


    Product Features:

    1. Simultaneously test the DC resistance of the three-phase winding of the transformer.

    2. For on load tap changers, there is no need for discharge, and the tap changer can be directly adjusted. The measurement time is one-third of traditional single-phase measurement, which can greatly shorten the working time and labor intensity.

    3. The direct resistance meter adopts a large screen LCD display with a fully Chinese graphical interface, which is clear and intuitive, and the operation is very simple.

    4. And equipped with a panel printer and large capacity non-volatile memory, it can conveniently store and print measurement results.

    5. The test data is stable, fast, and has good repeatability, making it the best choice for on-site measurement of transformer DC resistance.


    Matters needing attention:

    1. When measuring an unloaded voltage regulating transformer, the discharge must be exited before switching the tap changer. The tap changer can only be switched after the discharge indication is complete

    2. It is not allowed to dismantle the wiring during the measurement process.

    3. If the charging progress bar and current display value remain stagnant for a long time, the measured winding resistance may exceed the current measurement range, and the current may not reach the preset value. At this point, you can press the 'Exit' button to return, select the current again, and try again.

    4. When replacing the fuse and accessories, please use the same model as this instrument








    Bạn cũng có thể thích

    • Có bất kỳ câu hỏi nào!

      ĐỪNG ngần ngại LIÊN HỆ VỚI CHÚNG TÔI BẤT CỨ LÚC NÀO
      Liên hệ chúng tôi
    • Ghé thăm chúng tôi

      Tòa nhà 6, Khu công nghiệp Cơ khí Quang học Thung lũng Quang học, 84 Đường Gaoxin 5,
      Khu phát triển công nghệ mới Hồ Đông, thành phố Vũ Hán, tỉnh Hồ Bắc, Trung Quốc

    • Gửi email cho chúng tôi

      qiao@hvtest.cc

    • Gọi cho chúng tôi

      +86-15871365102