qiao@hvtest.cc15871365102
  • UHV-901 Integrated CT PT Field Calibration Tester

    Measures CT/PT ratios (1%-200%) and phase angles with high accuracy, featuring auto-regulated power supply, touchscreen interface, and compliance with national standards for reliable field and lab testing.

    Product Details of UHV-901 Integrated CT PT Field Calibration Tester

    Product Introduction

    This Integrated CT PT Field Calibration Tester measures current/voltage transformer ratios (1%-200%) and phase differences in compliance with national standards, while also supporting direct transformer ratio and polarity tests. Featuring automatic linear-adjustment DC/AC power supply, advanced digital processing, and a stable measurement circuit, it ensures exceptional accuracy and reliability. The user-friendly 800×600 LCD touchscreen with WINCE system offers intuitive English operation, wiring guidance, and data storage, making it ideal for field and laboratory transformer testing.


    Key Features:

    1、Integrated Solution

    Employs small-signal measurement technology for complete CT/PT error testing

    Eliminates need for external standard transformers, boosters, or load boxes

    Built-in 0.02-class reference standard (equivalent to 0.05S-class accuracy)

    2、Advanced Testing Capabilities

    Wide measurement range: 1%-200% (including S-class CTs)

    Measures ratio/phase errors at any load point (upper/lower limits)

    Automatic polarity/ratio detection for known & unknown transformers

    Complies with national standards for VT testing (20%-120% range)

    3、Smart Operation

    800×600 LCD with full Chinese interface

    Auto-wiring detection with error alerts

    On-site data storage & USB data export

    Shock-resistant casing (weight <6kg; 472×355×168mm)

    4、Efficient Workflow

    Near-power-frequency testing minimizes interference

    Instant pass/fail determination

    One-click report generation per national standards


    Applications:

    • Field calibration of metering devices

    • Standard/non-standard transformer verification

    • Unknown transformer parameter identification


    Thông số sản phẩm

    (1)

    CT ratio range5A/5A~25000A/5A (5A/1A~5000A/1A) turn ratio error ± 0.2%
    Error measurement range5A/5A~5000A/5A(5A/1A~5000A/1A)
    Accuracy range of the tested current transformer1.0, 0.5, 0.5S, 0.2, and 0.2S
    CT error accuracy0.02 level

    (2)

    PT ratio rangeFull range measurement (electromagnetic type) ± 0.2%
    Error measurement rangePrimary voltage:3-220kV/(non-standard primary voltage is also acceptable) Secondary voltage: 3kV/100V、3kV//100V/;6kV/100V、6kV//100V/;6.3kV/100V、 6.3kV//100v/;10kV/100V、10kV//100V/;10.5kV/100V、10.5kV//100V/;13.8kV/100V、13.8kV//100V/;15kV/100V、15kV//100v/;15.75kV/100V 、15.75kV//100V/;18kV/100V、18kV//100V/ ;20kV/100v、 20kV//100v/;35kV/100V、35kV//100V/;66kV//100v/; 110kV//100V/;220kV//100V/
    Power factor0.0-1.0
    PT error accuracy0.05 level
    DC resistance0.0-0.1 Ω ± 3%
    0.1-50Ω ±1%
    Nhiệt độ môi trường0-40℃
    Power consumption of the whole machine30W (static) and 150W (working)
    Nhiệt độ môi trường0-40℃
    Độ ẩm môi trường<85% at 25℃
    Whole machine weight6.0Kg
    Whole machine volume472mm × 355mm × 168mm









    Bạn cũng có thể thích

    • Có bất kỳ câu hỏi nào!

      ĐỪNG ngần ngại LIÊN HỆ VỚI CHÚNG TÔI BẤT CỨ LÚC NÀO
      Liên hệ chúng tôi
    • Ghé thăm chúng tôi

      Tòa nhà 6, Khu công nghiệp Cơ khí Quang học Thung lũng Quang học, 84 Đường Gaoxin 5,
      Khu phát triển công nghệ mới Hồ Đông, thành phố Vũ Hán, tỉnh Hồ Bắc, Trung Quốc

    • Gửi email cho chúng tôi

      qiao@hvtest.cc

    • Gọi cho chúng tôi

      +86-15871365102