  • UHV-740 Capacitive Voltage Transformer Field Calibration Instrument

    Provides accurate ratio and phase error measurement for voltage transformers in electrical power testing applications.

    Product Details of UHV-740 Capacitive Voltage Transformer Field Calibration Instrument

    Product Introduction

    We are a professional manufacturer and supplier of high-voltage power testing equipment in China.UHV-740 Capacitive Voltage Transformer Field Calibration Instrument GIS Field Calibrator simplifies on-site error calibration for electromagnetic (PT) and capacitive voltage transformers (CVT), overcoming traditional challenges of complex wiring, bulky equipment, and high-voltage requirements. This all-in-one solution performs accurate low-voltage measurements across multiple ratios (6kV-220kV/100V), integrating innovative technologies like variable-frequency power supply, common platform design, and simulated voltage loads.

    HTY_2338HTY_2345HTY_2342


    Key Features & Benefits

    1、All-in-One Testing Solution

    Eliminates need for boost sources/load boxes by using voltage transformer load curve extrapolation to measure PT/CVT errors (ratio/phase) at 20%-120% loads, fully compliant with national standards.

    Comprehensive Parameter Measurement

    2、Single device tests:

    PT/CVT ratio & phase errors

    CVT partial voltage ratio/capacitance

    Intermediate PT ratio/voltage

    DC resistance

    Polarity/ratio/wiring checks

    3、Efficiency & Safety

    One-click complete testing reduces errors/risks

    <4kV operation with multi-layer protection

    16GB storage (millions of datasets)

    Fast frequency-conversion tech with anti-interference

    4、User-Centric Design

    WINCE OS with dual-mode operation (touchscreen/mouse)

    Intuitive wiring diagrams for foolproof connections

    Dual USB ports for instant data export


    Thông số sản phẩm

    Các thông số kỹ thuật

    Environmental conditionNhiệt độ(5~40)℃
    Độ ẩm tương đối<80%(25℃)
    Sea level<4500m
    Tần số nguồn50±0.5Hz
    Type of the voltage transformer to be measuredGIS Electromagnetic (PT), Capacitive Voltage Transformer (CVT)
    Primary voltage6-500kV/√3(Non-standard primary voltage is also acceptable)
    Secondary voltage100V,100V/√3,110V,110V/√3,100/3V
    Accuracy of error measurement0.05%
    Partial pressure ratio measurement accuracy0.5%
    Measuring accuracy of partial voltage capacitance2%
    DC resistance measurement accuracy0-0.1Ω3%
    0.1-501%
    Internal standard voltage transformer sectionRatio range6kV/100V、6kV/√3 /100V/√3
    10kV/100V、10kV/√3 /100V/√3
    35kV/100V、35kV/√3 /100V/√3
    110kV/100V、110kV/√3 /100V/√3
    220kV/100V、220kV/√3 /100V/√3
    330kV/100V、500kV/√3 /100V/√3
    Accuracy class0.02%
    Verification part of the calibratorDải điện áp0-100V (dial indicator error 0.5%)
    Ratio error0.001%-3% (100V)
    Angular difference0.00′-50′(100V)
    Lỗi△X=±(2%×X+2%×Y±2 words)
    △Y=±(2%×X+2%×Y±2 words)
    Admittance0.1ms-99.9ms
    Lỗi△X=±(2%×X+2%×Y±2 words)
    △Y=±(2%×X+2%×Y±2 words)
    Overall dimensions (mm)496*394*185
    Weight (kg)14.0


    Application Scenarios

    Substation on-site testing — Before commissioning of newly built or expanded substations, perform ratio, phase error, polarity, and wiring verification on PT/CVT.

    Substation operation and maintenance — Regular preventive testing, equipment condition inspection, and fault diagnosis to determine whether the PT/CVT has any abnormal parameters.

    GIS equipment testing — On-site verification and parameter testing of electromagnetic PTs and CVTs within GIS.

    Power metering / calibration — Checks the ratio and phase error of metering-grade PTs/CVTs, suitable for metering inspection, calibration, and related work.

    Power equipment manufacturing and engineering commissioning — Factory testing by PT/CVT/GIS manufacturers; on-site acceptance testing by EPC contractors, electrical installation companies, and third-party testing organizations.


    Frequently Asked Questions

    Q:What types of voltage transformers can the UHV-740 test? 

    A:The UHV-740 is designed for testing electromagnetic voltage transformers (PTs) and capacitive voltage transformers (CVTs), including voltage transformers installed in GIS systems. 

    Q:Can the UHV-740 test both PT and CVT? 

    A:Yes. The UHV-740 supports comprehensive testing of both PTs and CVTs, including ratio error, phase error and other relevant parameters. 

    Q:Can the UHV-740 be used for GIS applications? 

    A:Yes. The UHV-740 is suitable for on-site testing of electromagnetic PTs and CVTs in GIS equipment.

    Q:What are the main advantages of the UHV-740?
    A:Its main advantages
    include integrated PT/CVT testing functions, portable field operation, reduced dependence on conventional test equipment, multiple measurement functions and simplified on-site testing.








    Bạn cũng có thể thích

    • Có bất kỳ câu hỏi nào!

      ĐỪNG ngần ngại LIÊN HỆ VỚI CHÚNG TÔI BẤT CỨ LÚC NÀO
      Liên hệ chúng tôi
    • Ghé thăm chúng tôi

      Tòa nhà 6, Khu công nghiệp Cơ khí Quang học Thung lũng Quang học, 84 Đường Gaoxin 5,
      Khu phát triển công nghệ mới Hồ Đông, thành phố Vũ Hán, tỉnh Hồ Bắc, Trung Quốc

    • Gửi email cho chúng tôi

      qiao@hvtest.cc

    • Gọi cho chúng tôi

      +86-15871365102