qiao@hvtest.cc15871365102
  • Precautions for Transformer Winding Deformation Testing Machine

    The UHV power professional production transformer winding deformation tester can help many power workers conduct various power tests more conveniently.

    HTY_1355

    Precautions for determining transformer winding deformation:

    a) The necessary conditions for transformer winding deformation are outlet short circuit, near-field short circuit, multiple overcurrent actions, and collisions during transportation;

    b) The frequency response curves of the low-frequency part (tens of kHz) can generally overlap well, otherwise it is suspected that the test wiring has poor contact;

    c) Generally speaking, transformers of 35kV and below (including those undergoing factory renovation) may have poor frequency response characteristics, and original data comparison should be retained during handover;

    d) The measured frequency response curve is generally between+20 and -80 dB. If exceeded, check whether the test circuit has poor contact or disconnection;

    e) When the angle winding is tested separately, the three-phase frequency response characteristics may not be consistent;

    f) Balancing windings may result in inconsistent three-phase frequency response characteristics;

    g) Severe distortion of windings can affect the frequency response characteristics of adjacent windings;

    h) Due to poor craftsmanship, the frequency response characteristics of transformer windings may not be consistent in some small factories and on-site maintenance transformers;

    i) There is evidence to suggest that temperature has an impact on frequency response characteristics;

    j) When the entangled winding has transposed conductors, the frequency response characteristics of the transformer winding may not be consistent;

    Bạn cũng có thể thích

    • Có bất kỳ câu hỏi nào!

      ĐỪNG ngần ngại LIÊN HỆ VỚI CHÚNG TÔI BẤT CỨ LÚC NÀO
      Liên hệ chúng tôi
    • Ghé thăm chúng tôi

      Tòa nhà 6, Khu công nghiệp Cơ khí Quang học Thung lũng Quang học, 84 Đường Gaoxin 5,
      Khu phát triển công nghệ mới Hồ Đông, thành phố Vũ Hán, tỉnh Hồ Bắc, Trung Quốc

    • Gửi email cho chúng tôi

      qiao@hvtest.cc

    • Gọi cho chúng tôi

      +86-15871365102